Flow Control Retrofit Increases Safety For German Intercity Express

It was only a few years ago that the first generation of the German Intercity-Express, the ICE1, was making headlines - but for the wrong reasons. Problems due to overheating of the engine caused by ventilation failures were frequently reported, and ensuing fires caused damage that ran into several millions of pounds. Ventilators providing cooling air to the traction power converters, are powered by auxiliary generators, which themselves are self-ventilated. The fires were the result of failures of this self-ventilation system. A failure in the supply of cooling air can have several causes. Firstly, the doors of the cabinets containing the power converter rectifiers must always be closed. If this is not the case, the amount of cooling air will not be sufficient to cool all the electronic components. Secondly, the air exit shutters are closed during exterior cleaning to prevent cleaning agent vapours coming into contact with the electronic components. After cleaning, these shutters should open automatically, but if they remain closed the auxiliary generator will overheat. Deutsche Bahn's solution was to fit Turck Banner calorimetric type flow controls* directly behind the ventilator to monitor the cooling flow. If the flow remains below the set point for a certain period, the sensor signals an alarm message to the control cab, the train driver receiving both a visible and an audible error-message. The decision to opt for calorimetric flow controls was based on their tolerance of deposit build-up. They are also simple to mount and adjust, compared with alternative arrangements such as differential pressure systems or impeller flow meters. Indeed, the generally slow response of calorimetric flow controls was an advantage in this case, because a more sensitive system would tend to issue superfluous error messages in response to standard air fluctuations. The sensors are adjusted by means of a potentiometer, assisted by a dual colour LED, which turns from green to red if the minimum flow is under-ranged. If the flow stays below the minimum value for more than a minute, the sensor's transistor output, which is coupled to a timer module, sends an error message to the control cab. If the fault is recovered and a sufficient amount of cooling air is supplied again, the output transistor changes state and the LED illuminates green. *Calorimetric flow control is based on the heat loss principle. The sensing probe has two temperature-dependent measuring elements one of which is heated electrically. When fluid moves over the outside of the sensor, heat is conducted away from it and the temperature of the heated sensing probe falls. The measuring element, that is not heated electrically, assumes the temperature of the stationary or flowing medium. The difference between the two temperatures is thus a measure of the speed of flow. 9

Previous Article Hinkley Point C powers up ultrasound fish protection
Next Article Air-con could produce more CO2 than whole of US by 2050
Related Posts
fonts/
or