Twelve-Pulse Rectifier Cuts Harmonic Distortion By 80% .

Twelve-pulse rectifier cuts harmonic distortion by 80% Fitted to the ACS 600 range of medium power ac drives, ABB's integrated 12-pulse input rectifier module will reduce total harmonic (THD) by up to 80% compared with conventional six-pulse supplies. The 12-pulse supply is generated by two six-pulse rectifiers, connected to a three-phase system via a three-winding, phase-shift transformer. Phase shifting the secondary windings by 30o significantly reduces the sum of the secondary currents in the primary windings, resulting in a current THD of between 5 and 15%. This would be more like 40 or 50% in a six-pulse installation.